Keep the cable terminated
The divided washer can be fitted around the existing entry thread, avoiding cable disconnection for the washer replacement.
BLAYDS PRODUCTS · CABLE GLANDS UK
Replace a missing or damaged entry washer.
Keep the existing cable termination.
The two-part RetroSeal washer fits around an existing cable gland to renew the seal between the gland and enclosure, without disconnecting and re-terminating the cable.
REPAIR THE ENTRY SEAL
A conventional one-piece washer can be difficult to replace once a cable has been terminated. RetroSeal opens into two parts, so it can be fitted at the gland-to-enclosure interface.
The gland is loosened to create the fitting gap, the two washer sections are joined around the entry thread, and the gland is reassembled in accordance with the manufacturer’s instructions.
This approach can reduce the work involved in replacing a worn, damaged or missing IP washer, particularly where disconnecting wiring would make a straightforward repair more disruptive.
The divided washer can be fitted around the existing entry thread, avoiding cable disconnection for the washer replacement.
Retain a serviceable gland and reduce the dismantling, materials and labour associated with replacing a conventional washer.
Interlocking PA6 nylon sections form a complete washer at the equipment-to-gland interface.
SELECT BY GLAND ENTRY THREAD
Match the washer to the gland’s entry thread size.
Pack quantities vary by size.
| Entry thread size | Manufacturer part code | Washers per pack | Enquire by size |
|---|---|---|---|
| M20 | RETROSEAL-M20 | 10 | Enquire about M20 |
| M25 | RETROSEAL-M25 | 10 | Enquire about M25 |
| M32 | RETROSEAL-M32 | 10 | Enquire about M32 |
| M40 | RETROSEAL-M40 | 5 | Enquire about M40 |
| M50 | RETROSEAL-M50 | 5 | Enquire about M50 |
| M63 | RETROSEAL-M63 | 5 | Enquire about M63 |
M20–M63 identifies the gland’s metric entry thread, rather than cable diameter. Ask us to confirm suitability, pricing and availability for your installation.
PRODUCT SPECIFICATION
Manufacturer information for the RetroSeal two-part cable gland IP washer.
Open manufacturer datasheet| Product type | Two-part retro-fit cable gland IP washer |
|---|---|
| Sealing position | Between the cable gland and equipment or enclosure |
| Material | PA6 nylon |
| Thickness | 3 mm |
| Environmental resistance | UV-resistant construction; manufacturer also describes ozone resistance |
| Ingress protection | Manufacturer reports independent IP66/IP67 testing to IEC 60529. Installation sheet states IP66 without sealant and IPX7 with sealant. |
| Available thread sizes | M20, M25, M32, M40, M50 and M63 |
| Operating temperature | Confirm the applicable range with Cable Glands UK before specification. |
The manufacturer’s datasheet and installation sheet give different temperature ranges. Obtain confirmation for your application. For IP67 duty, follow the manufacturer’s specified sealing method and confirm the required compound.
HOW THE TWO-PART DESIGN FITS
Installation must be carried out by qualified personnel. Follow site isolation procedures, the gland manufacturer’s instructions and all applicable requirements, including those for hazardous areas.
Loosen the backnut and, where applicable, the middle nut to avoid twisting the cable or damaging the braid.
Unscrew the gland from the enclosure by at least 5 mm. A clearance-hole entry secured by a locknut requires safe access inside the enclosure.
Clean the mating faces of the gland and equipment before fitting the replacement washer.
The installation sheet calls for a small amount of electrical insulating compound on all four split ends and on the front and rear washer faces.
Place both halves around the entry thread and click them together. The joint is designed to assemble in one orientation.
Secure the gland into the threaded entry or with the internal locknut, as appropriate for the enclosure.
Reassemble the remaining gland components to the gland manufacturer’s instructions and specified torque, then complete the required inspection.
This overview supports selection; use the full manufacturer’s instructions for the installation. RetroSeal’s IP test claim does not establish hazardous-area certification for a complete gland and enclosure assembly.
DOCUMENTS FOR YOUR PROJECT
Original documents from Blayds.
PDFs open in a new tab.
RetroSeal is a two-part PA6 nylon washer for the seal between a cable gland and an enclosure. It allows a missing, worn or damaged entry washer to be replaced around an existing gland installation.
The split design is intended to avoid disconnecting and re-terminating the cable. The gland still needs to be loosened and partly disassembled. Safe access inside the enclosure may also be needed, depending on the entry arrangement.
Blayds reports independent IP66/IP67 testing. Its installation sheet specifies IP66 without sealant and IPX7 with sealant. Follow the required installation method and confirm the compound for the protection level your application needs.
M20, M25 and M32 are listed in packs of 10 washers. M40, M50 and M63 are listed in packs of 5. Select by the gland entry thread size, rather than the cable diameter.
Have a qualified person assess the complete gland and equipment assembly against its certification, manufacturer’s instructions and site requirements. An IP rating alone does not confirm that an accessory is suitable for every hazardous-area installation.
Send Cable Glands UK the required thread size, number of packs and details of your installation using the form below, or call 0161 874 1480.
SPEAK TO CABLE GLANDS UK
Send your RetroSeal size, pack quantity and application details. We’ll help you check the right option and confirm pricing and availability.
0161 874 1480Supporting cable gland selection and maintenance enquiries from Trafford Park, Manchester.
RetroSeal® is a Blayds product. Manufacturer documents should be checked for the latest application and installation requirements.
PLAN YOUR MAINTENANCE COSTS
Compare replacing a conventional cable gland entry washer with fitting a RetroSeal split washer around an existing termination. Enter your project figures to estimate the difference.
The starting figures and presets are illustrative examples. The washer prices shown are not Cable Glands UK quotations.
Complete all inputs using non-negative numbers. Gland quantities and crew sizes must be whole numbers of at least one.
Estimated project saving
Calculations appear when the calculator is ready.
| Cost item | Conventional | RetroSeal |
|---|---|---|
| Fitting / replacement labour | — | — |
| Washer supply | — | — |
| Re-testing labour | — | — |
| Permits / isolation | — | — |
| Production downtime | — | — |
| Project total | — | — |
Adjust the inputs to compare your project costs.
Ask Cable Glands UK for RetroSeal pricingKeep replacement and testing times separate to avoid counting the same work twice. The example scenarios assume that RetroSeal avoids conventional re-testing, permit and production downtime costs; edit the additional RetroSeal fields when that assumption does not fit your site.
Illustrative estimate based on your inputs. Example fitting times, prices and operating costs are not guaranteed results or confirmed CGUK prices. Site procedures, isolation, inspection and installation requirements still apply. Costs not entered here, including any additional materials or taxes, are excluded.